Experimental study of the influence of electric receivers of a private housing stock in rural areas on the level of distortion of the sinusoidal voltage and current in the network of 0.38 kV

Abstract

Experimental study of the influence of electric receivers of a private housing stock in rural areas on the level of distortion of the sinusoidal voltage and current in the network of 0.38 kV

Terentyev P.V., Filatov D.A., Chesnokov M.V., Korablev A.A.

Incoming article date: 10.01.2020

A large number of power receivers with non-linear current-voltage characteristics with a pulsed mode of operation appeared in residential buildings, which leads to the generation of 0.38 kV higher harmonic current components into the electric network, large values ​​of these harmonics lead to a deterioration in the shape of the network voltage curve. The purpose of the work is to study the harmonics of current generated by electrical receivers of residential buildings, and their influence on the coefficient of non-sinusoidality of the network voltage of 0.38 kV. It has been established that the greatest negative impact on the electric network is exerted by electronic devices with switching power supplies, such as PCs, laptops and netbooks, as well as dishwashers and LED lamps with a socle E14 and E27, whose total harmonic current component coefficient is 85% ≤ THDI ≤ 205%. In the Matlab Simulink program, a simulation model of a 0.38 kV network of a residential building is simulated, which allows the study of the total distortion coefficient of the current KI and voltage KU in the ASU. With the installed non-linear load power more than double the linear load, the coefficient of non-sinusoidality of the voltage in the network of 0.38 kV may exceed the values ​​established by GOST 32144-2013.

Keywords: power supply system, electric network, quality of electric energy, voltage harmonics, current harmonics, electromagnetic compatibility, power receiver